Product and Technical Support and Downloadable Order and Return Forms

Program Code 22

Micro-Speed® CX® and Smart-Move®

Manual Addendum for MSMR and CXR Version 2.2 with motor thermal protection.

 

 

IMPORTANT:
U22 must be set to total motor FLA and U26 must be set to “ON” or “1” unless separate motor thermal protection is provided by user.

CAUTION: Do not set U22 greater than total motor nameplate amps.

Viewing Current:
While running you can view the current by holding down the “Increase” button on the front of the drive.

Additional U Parameters:


Parameter        Parameter Name                                  Settings                          Default
U22                     Motor Nameplate FLA                          ----, Range in Amps      ----
                            Set to total motor nameplate FLA.
                             ----   =  Not set.  Will give a P.C.22 code if U26 not set to off.

U26                     Thermal Mode                                       OFF, on, 1                        on
                            oFF  =      Off.  Separate motor thermal protection is required.
                            on    =     On.  Drive can trip with an F2. Motor needs to cool.
                              1    =      On for hoist motion.  Unit will inhibit the Fwd(up) direction     
                                             until motor has time to cool off. Hoist can be run down to
                                             set the load down.
                                             Hoist up must be connected to the F (forward) terminal
                                             on the drive.


Additional PC Code:

P.C.22                 Program Code 22                                U22 is not set & U26 is not off.
                             The default for U22 is ----  (= not set).   The total motor nameplate
                             FLA must be entered. U26 can be turned off as well if separate
                             motor thermal protection is provided.